Marque:SCHNEIDER ELECTRIC
Ref Product:EZ9R36425
Ref Mcmining:SCEZ9R36425
| Description | |
| Residual current circuit breaker (RCCB), Easy9, 4P, 25A, AC type, 30mA |
|
| EZ9R36425 |
|
| Specifications |
|
| Main |
|
| Range of product |
Easy9 |
| Product or component type |
Residual current circuit breaker (RCCB) |
| Device short name |
Easy9 RCCB |
| Poles |
4P |
| Neutral position |
Left |
| [In] rated current |
25 A |
| network type |
AC |
| Earth-leakage sensitivity |
30 mA |
| Earth-leakage protection time delay |
Instantaneous |
| Earth-leakage protection class |
Type AC |
| Rated breaking and making capacity |
500 A |
| Rated conditional short-circuit current |
Easy9 MCB: 6000 A 25 A |
| Complementary |
|
| Device location in system |
Outgoer |
| Network frequency |
50/60 Hz |
| [Ue] rated operational voltage |
400 V AC 50/60 Hz |
| Residual current tripping technology |
Voltage independent |
| [Ui] rated insulation voltage |
440 V AC |
| [Uimp] rated impulse withstand voltage |
4 kV |
| Surge current |
250 A |
| Contact position indicator |
Yes |
| Control type |
Toggle |
| Mounting mode |
Clip-on |
| Mounting support |
DIN rail |
| Comb busbar and distribution block compatibility |
Top: YES |
| Connection pitch |
18 mm between phases |
| 9 mm pitches |
8 |
| Height |
82 mm |
| Width |
72 mm |
| Depth |
72 mm |
| Colour |
Grey (RAL 7035) |
| Mechanical durability |
5000 cycles |
| Electrical durability |
AC: 2000 cycles 400 V AC 50/60 Hz |
| Connections - terminals |
Tunnel type terminal (top or bottom) 1…35 mm² rigid |
|
Tunnel type terminal (top or bottom) 1…25 mm² flexible |
|
| Tightening torque |
3.5 N.m top or bottom |
| Environment |
|
| Standards |
IEC 61008-1 |
| Product certifications |
CE |
| IP degree of protection |
IP20 |
| Pollution degree |
2 conforming to IEC 61008-1 |
| Tropicalisation |
2 |
| Relative humidity |
95 % at 55 °C |
| Ambient air temperature for operation |
-5…60 °C |
| Ambient air temperature for storage |
-40…85 °C |