Marque:SCHNEIDER ELECTRIC
Ref Product:SCEZ9R36240
Ref Mcmining:SCEZ9R36240
| DESCRIPTION | |
Easy9 Residual Current Circuit Breaker - 2P - 40A - 30 mA - AC type - 230 V |
|
| EZ9R36240 | |
| Main Specifications | |
| Range of product | Easy9 |
| Product or component type | Residual current circuit breaker (RCCB) |
| Device short name | Easy9 RCCB |
| Poles | 2P |
| Neutral position | Left |
| [In] rated current | 40 A |
| network type | AC |
| Earth-leakage sensitivity | 30 mA |
| Earth-leakage protection time delay | Instantaneous |
| Earth-leakage protection class | Type AC |
| Rated breaking and making capacity | 500 A |
| Rated conditional short-circuit current | Easy9 MCB: 6000 A 40 A |
| Complementary Specifications | |
| Device location in system | Outgoer |
| Network frequency | 50/60 Hz |
| [Ue] rated operational voltage | 230 V AC 50/60 Hz |
| Residual current tripping technology | Voltage independent |
| [Ui] rated insulation voltage | 440 V AC |
| [Uimp] rated impulse withstand voltage | 4 kV |
| Surge current | 250 A |
| Contact position indicator | Yes |
| Control type | Toggle |
| mounting mode | Clip-on |
| mounting support | DIN rail |
| Comb busbar and distribution block compatibility | Top: YES |
| Connection pitch | 18 mm between phases |
| 9 mm pitches | 4 |
| Height | 82 mm |
| Width | 36 mm |
| Depth | 72 mm |
| Colour | Grey (RAL 7035) |
| Mechanical durability | 5000 cycles |
| Electrical durability | AC: 2000 cycles 230 V AC 50/60 Hz |
| Connections - terminals | Tunnel type terminal (top or bottom) 1…35 mm2 rigid Tunnel type terminal (top or bottom) 1…25 mm2 flexible |
| Tightening torque | 3.5 N.m top or bottom |
| Environment | |
| Standards | IEC 61008-1 |
| Product certifications | CE |
| IP degree of protection | IP20 |
| Pollution degree | 2 conforming to IEC 61008-1 |
| Tropicalisation | 2 |
| Relative humidity | 95 % at 55 °C |
| Ambient air temperature for operation | -5…60 °C |
| Ambient air temperature for storage | -40…85 °C |