Marque:SCHNEIDER ELECTRIC
Ref Product:EZ9R66425
Ref Mcmining:SCEZ9R66425
| Description | |
| Residual current circuit breaker (RCCB), Easy9, 4P, 25A, AC type, 300mA |
|
| EZ9R66425 |
|
| This is a Easy9 residual current circuit breaker (RCCB).
It is a 4P circuit breaker with In rated current of 25A, AC type protection
class and a 300mA earth leakage sensitivity. This product protects against
electrical shock by indirect contact and fire hazards. It also has protection
against fire hazards due to persistent earth fault current. This product has
a positive contact indications with fault tripping indication on the front
panel by the position of the handle (0-I engraved). This is dedicated for
residential and small commercial buildings market segment. This product is compliant
with IEC 61008-1 standard. The (Im/IΔm) rated breaking and making short
circuit capacity is 500A. The (Inc/IΔc) conditional rated short circuit
current is 6000A. The electrical endurance is up to 2000 cycles. The
mechanical endurance is up to 5000 cycles. The Ue operational voltage is
400VAC. The Ui rated insulation voltage is 440VAC. The Uimp rated impulse
withstand voltage is 4kV. The frequency is 50Hz or 60Hz. It is DIN rail
mountable. The width in 9mm pitches is 8. The product color is light grey
(RAL7035). The dimensions are (W) 72mm x (H) 82mm x (D) 72mm. It has an IP20
degree of protection. It becomes IP40 once in modular enclosure according to
IEC/EN 60529 standard. The operating temperature is from -5°C to 60°C. The
storage temperature is from -40°C to 85°C. |
|
| Specifications |
|
| Main |
|
| Range of product |
Easy9 |
| Product or component type |
Residual current circuit breaker (RCCB) |
| Device short name |
Easy9 RCCB |
| Poles |
4P |
| Neutral position |
Left |
| [In] rated current |
25 A |
| network type |
AC |
| Earth-leakage sensitivity |
300 mA |
| Earth-leakage protection time delay |
Instantaneous |
| Earth-leakage protection class |
Type AC |
| Rated breaking and making capacity |
500 A |
| Rated conditional short-circuit current |
Easy9 MCB: 6000 A 25 A |
| Complementary |
|
| Device location in system |
Outgoer |
| Network frequency |
50/60 Hz |
| [Ue] rated operational voltage |
400 V AC 50/60 Hz |
| Residual current tripping technology |
Voltage independent |
| [Ui] rated insulation voltage |
440 V AC |
| [Uimp] rated impulse withstand voltage |
4 kV |
| Surge current |
250 A |
| Contact position indicator |
Yes |
| Control type |
Toggle |
| Mounting mode |
Clip-on |
| Mounting support |
DIN rail |
| Comb busbar and distribution block compatibility |
Top: YES |
| Connection pitch |
18 mm between phases |
| 9 mm pitches |
8 |
| Height |
82 mm |
| Width |
72 mm |
| Depth |
72 mm |
| Colour |
Grey (RAL 7035) |
| Mechanical durability |
5000 cycles |
| Electrical durability |
AC: 2000 cycles 400 V AC 50/60 Hz |
| Connections - terminals |
Tunnel type terminal (top or bottom) 1…35 mm² rigid |
|
Tunnel type terminal (top or bottom) 1…25 mm² flexible |
|
| Tightening torque |
3.5 N.m top or bottom |
| Environment |
|
| Standards |
IEC 61008-1 |
| Product certifications |
CE |
| IP degree of protection |
IP20 |
| Pollution degree |
2 conforming to IEC 61008-1 |
| Tropicalisation |
2 |
| Relative humidity |
95 % at 55 °C |
| Ambient air temperature for operation |
-5…60 °C |
| Ambient air temperature for storage |
-40…85 °C |